14. Appendix E
14.1. Fieldbus Wiring Considerations
Preference
Type
1
#18 AWG, shielded, twisted
pair
2
#22 AWG, multiple-twisted,
pairs with overall shield
3
#26 AWG, multiple-twisted,
pairs without shield
4
#16 AWG, multiple
conductor, no twisted pairs
with overall shield
Another rule of thumb based on Fieldbus Foundation published guidelines is for the
length of spurs and how many devices can be on various lengths of cable as listed in the
following table.
Number of Devices
ATTENTION
The spur length limitations are for spurs with one device each. Please refer to
the Fieldbus Foundation AG-140 Wiring and Installation Guide for rules on
multiple devices per spur.

Cable guidelines summary

Total cable length is the sum of trunk and spur lengths. If different cable preference types
are used, apportion each type against its limit and be sure the total is less than one (1).
514
Experion PKS Series A Fieldbus Interface Module User's Guide
Description
(Meters/Feet)
1900/6233
1200/3937
400/1312
200/656
1 to 12
13 to 14
15 to 18
19 to 24
25 to 32
Honeywell
Distance
Resistance
(Ohms per
km)
22
56
132
20
Maximum Spur Length (Meter/Feet)
120/394
90/295
60/197
30/98
No spurs allowed
Attenuation
dB per km
3
5
8
8
R400