Step
6
Click the Close button to acknowledge
any errors or skip this Step, if no errors
are detected.
7
Repeat Steps 4 to 6 for other CMs, as
required.
TIP
It is a good idea to record the Tag and Address assignments for the failed device
before deleting it.
8
Right-click the failed device icon and
select Force Delete from the popup
menu.
9
Click the Delete Selected object(s)
button.
10
In Project tab, double-click the CM
(pidloop) that was deleted from the
Monitoring tab.
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
8.1. Adding, Removing and Replacing Components
Action
Honeywell
8. Maintenance, Checkout, and Calibration
Result
Deletes CM (pidloop) from CEE folder
along with fieldbus block (FFAI101) from
device (ST101) in Monitoring tab, for this
example.
Opens Force Delete dialog.
Deletes Failed device from the Link folder
in Monitoring.
Opens CM in control chart.
301