Advertisement

5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
Step
4
Be sure the correct communications
driver name appears in the Driver Name
field. If it doesn't, select the correct one
from the field's dropdown list. Press
<Tab>.
5
Click
button to select the Supervisory
Mac Address set in the ControlNet
module connected to the Supervisory
network. Use 01 for this example. Press
<Tab>.
6
Click
button to select the Slot
number where the ControlNet Module
connected to the Supervisory network is
installed. Use 00 for this example. Press
<Tab>.
126
Experion PKS Series A Fieldbus Interface Module User's Guide
Action
Honeywell
Result
Moves cursor to Supervisory MAC
Address field.
Moves cursor to Supervisory Slot
Number field.
Moves cursor to the Module Slot Number
field.
R400
July 2010