Dv_Lo_Alm - Honeywell Series A User Manual

Fieldbus interface module
Hide thumbs Also See for Series A:
Table of Contents

Advertisement

11. Appendix B
11.1. Standard Function Block Parameters
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

DV_LO_ALM

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks
438
Experion PKS Series A Fieldbus Interface Module User's Guide
Defines priority of the high deviation alarm.
Unsigned 8
0 to 63
C/Alert Priority
1
VIEW_4
Static
Initial value is 0
Record
Identifies the status and time stamp associated with the low
deviation alarm.
DS-71
C/Alarm
16
Dynamic
Read Only
The Data type consists of data that describes floating point
alarms. It uses the following five elements.
1 Unacknowledged
2 Alarm State
3 Time Stamp
4 Subcode
5 Value