BKCAL_OUT

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

BKCAL_OUT_D

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
11.1. Standard Function Block Parameters
Record
The value and status required by an upper block's
BKCAL_IN so the upper block may prevent reset windup
and provide bumpless transfer to closed loop control.
DS-65
O/Back Calculation Output
5
VIEW_3
Dynamic
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
Record
The output value and status provided to an upstream
discrete block that is used to provide bumpless transfer for
closed loop control.
DS-66
O/Back Calculation Output
2
VIEW_3
Dynamic
Honeywell
11. Appendix B
423