BAL_TIME

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

BIAS

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
11.1. Standard Function Block Parameters
Simple Variable
Specifies the time in seconds for the internal working value
of Bias or Ratio to return to the operator set value.
In PID block, specifies the time constant to be used to
move the integral term to obtain balance, when the output
is limited and the mode is Auto, Cas, or RCas.
Float
Positive
C/Contained
4
VIEW_4
Static
Initial value is 0
Simple Variable
Specifies the Bias value in engineering units to be used in
computing the function block output
Float
OUT_SCALE +/- 10 percent
C/Contained
4
VIEW_1, VIEW_3
Non-Volatile
Normally, the operator has permission to write these
values, but PROGRAM or LOCAL remove the permission
and grant it to a supervisory computer or a local control
panel.
Honeywell
11. Appendix B
421