11. Appendix B
11.1. Standard Function Block Parameters
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

SIMULATE_D

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks
480
Experion PKS Series A Fieldbus Interface Module User's Guide
DS-82
C/Simulate
11
Dynamic
The data type consists of simulate and transducer floating
point value and status and a simulate enable/disable
discrete. It uses the following five elements.
1: Simulate Status
2:Simulate Value
3: Transducer Status
4: Transducer Value
5: Simulate Enable/Disable
Record
Allows the transducer discrete input or output to the block
to be manually supplied, when SIMULATE is enabled.
When SIMULATE is disabled, the simulate value and status
track the actual value and status.