R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
11.1. Standard Function Block Parameters
discrete. It uses the following five elements.
1: Simulate Status
2:Simulate Value
3: Transducer Status
4: Transducer Value
5: Simulate Enable/Disable
Record
Defines the set point of any analog block.
DS-65
PV_SCALE +/- 10 percent
C/Set point
5
VIEW_1, VIEW_3
Non-Volatile
SP (SP_D) is normally written by an operator occasionally
while in Auto mode. It is not intended to be written as a
cascade setpoint input. Instead, a connection to CAS_IN is
intended to provide a value into SP (SP_D) when in Cas
mode and a write into RCAS_IN is intended to provide a
value into SP (SP_D) when in RCas mode. However, SP
(SP_D) may be updated when operating in ROut mode in
order to provide a reasonable setpoint, if failing from ROut
to Auto mode upon a failure of the ROUT_IN update.
The data type consists of the value and status of floating
point parameters that are Inputs or Outputs. It uses the
following two elements.
1 Status
2 Value
Honeywell
11. Appendix B
481