Viewing And Optimizing Link Schedule Configuration - Honeywell Series A User Manual

Fieldbus interface module
Hide thumbs Also See for Series A:
Table of Contents

Advertisement

Step
TIP
It may be a good idea to record the device's Tag name and Device ID for future
reference.
5
If a block type does exist, go to the
previous configuration procedures to
create, assign, configure, match, and
load the device.
If a block type does not exist, create
one using the vendor's DD files as
described in
device type from vendor DD in the
previous Configuration section.
TIP
It is possible that the uncommissioned device may have an earlier version of the
vendor's software (Device Rev). In this case, the device would appear to have no
matching block type even if one exists for the same device but it is for a different
software version. If the vendor supports flash upgrade of its device's firmware, you can
upgrade the device's firmware through this tab. Please see Upgrading Firmware in
Uncommissioned Device the next Section Maintenance, Checkout and Calibration for
more information.
A new Link Schedule must be loaded to the FIM and other LinkMaster devices anytime
there is a change that invalidates the current Link Schedule, such as adding a device,
removing a device, or making a configuration change.
6
Click the OK button to close the form.
7
This completes the check for
uncommissioned devices.

Viewing and optimizing Link schedule configuration

The following table summarizes how to call up a Link schedule configuration for
viewing in the control chart area of the Control Builder application. You can also interact
with the natural schedule to optimize it using the considerations listed below. Or, you can
configure the Link for the system to provide automatic schedule optimization as noted in
the following procedure.
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
6.3. Monitoring Fieldbus Functions Through Monitoring Tab
Action
Creating
a Fieldbus
Honeywell
Result
A block type must exist before a device
can be integrated with the system. The
illustration is for example purposes only.
6. Operation
267