Verify Mode

The Verify mode is used to display the parameters that have been changed from their default settings, either by
programming or by autotuning. "None" will be displayed if no settings have been changed.
The parameter A1-02 is the only parameter from the A1-
constant list if it has been changed before. The other parameters will not be displayed, even if they are differ-
ent from the default setting.
In the verify mode, the same procedures as used in the programming mode can be used to change settings. Use
the Increment, Decrement, and Shift/RESET keys to change a setting. When the DATA/ENTER key is pressed
the parameter setting are written and the display returns to the Monitor display.
Example Operations
In the example below the following settings have been changed from their default settings:
C1-01 (Acceleration Time 1)
C1-02 (Acceleration Time 2)
E1-01 (Input Voltage Setting)
E2-01 (Motor Rated Current).
Mode Selection Display
MENU
-ADV-
** Main Menu **
Programming
MENU
-VERIFY-
** Main Menu **
Modified Consts
MENU
-A.TUNE-
** Main Menu **
Auto-Tuning
MENU
-DRIVE-
** Main Menu **
Operation
MENU
-QUICK-
** Main Menu **
Quick Setting
MENU
Monitor Display
A
B
-VERIFY-
Accel Time 1
C1-01 = 002.0sec
(0.00 ~ 600.0)
"1.50sec"
ESC
-VERIFY-
Decel Time 2
C1-02 = 002.0sec
(0.00 ~ 600.0)
"1.50sec"
-VERIFY-
Input Voltage
E1-01=390VAC
(310~510)
"380VAC"
-VERIFY-
Motor Rated FLA
E2-01=
7.20A
(0.80 ~ 16.00)
"7.00A"
A
B
Fig 3.8 Operations in Verify Mode
group, which will be displayed in the modified
Setting Display
-VERIFY-
Accel Time 1
C1-01 = 002.0sec
(0.00 ~ 600.00)
"1.50sec"
ESC
-VERIFY-
Decel Time 2
C1-02 = 002.0sec
(0.00 ~ 600.0)
"1.50sec"
ESC
-VERIFY-
Input Voltage
E1-01= 390VAC
(310~510)
"380VAC"
ESC
-VERIFY-
Motor Rated FLA
E2-01 = 007.20A
(0.80 ~ 16.00)
"7.00A"
ESC
3
11
3-