Inverter Protection

Inverter Overheat Protection

The Inverter is protected against overheating using a thermistor that detects the heatsink temperature.
When the overheat temperature level is reached the inverter output is switched off.
To prevent a sudden and unexpected stop of the inverter due to an over temperature, an overheat pre-alarm can
be output. The temperature level for that pre-alarm can be set in parameter L8-02. Using parameter L8-03 the
inverter operation when an over temperature occurs can be selected.
If a multifunction output is set to this function the output is switched ON when the heatsink temperature
exceeds the overheat pre-alarm level set in L8-02.
Related Parameters
Parameter
No.
L8-02
Overheat pre-alarm level
L8-03
Inverter overheat (OH) pre-alarm operation selection
*1. The factory setting depends on the inverter capacity.
Multifunction Outputs (H2-01 to H2-03)
Set Value
20
Inverter overheat (OH)

Input Open Phase Protection

This function detects an open input phase by observing the DC bus voltage ripple level.
Related Parameters
Parameter
No.
L8-05
Input open-phase protection selection
The factory setting is enabled. It is not recommended to disable this function.
* This function is not available in software version VSL701034 and higher.
Name
Function
*
Name
Control Methods
Change
Factory
during
Setting
V/f
Operation
Vector
*1
No
A
95°C
3
No
A
Control Methods
Open
V/f
Loop
Vector
Yes
Yes
Control Methods
Change
Factory
Open
during
Setting
V/f
Operation
Vector
1
No
A
Closed
Open
Closed
Loop
Loop
Loop
Vector
Vector
(PM)
A
A
A
A
A
A
Closed
Closed
Loop
Loop
Vector
Vector
(PM)
Yes
Yes
Closed
Closed
Loop
Loop
Loop
Vector
Vector
(PM)
A
A
A
6-
6
47

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents