Control Circuit Wiring Precautions
The following precautions for wiring the control circuits must be considered.
Control circuit and main circuit wiring should be separated (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/
•
T2, W/T3,
The wiring for control circuit terminals MA, MB, MC, M1, M2, M3, M4, M5, and M6 (contact outputs)
•
should be separated from wiring to other control circuit terminals.
If an optional external power supply is used, it should be a UL Listed Class 2 power supply.
•
2
Twisted-pair or shielded twisted-pair cables should be used for control circuits to prevent operating faults.
•
The cable shields should be connected to the ground with the maximum contact area.
•
Cable shields have to be grounded on both cable ends.
•
22
2-
,
1,
2, and
3, PO, NO) and other high-power lines.