Speed Selection Sequence Using Digital Inputs
If the digital inputs are used for speed selection, the speed selection method and the speed priority depends on
the setting of parameter d1-18.
Parameter
No.
d1-18
Speed Priority Selection
Multi-Step Speed Operation 1/2 (Binary Input) (d1-18=0/3)
If d1-18 = 0
8 preset speed steps (defined in the parameters d1-01 to d1-08) can be selected using 3 binary coded digital
inputs. The Up/Down command starts the inverter. It stops when the Up/Down command is removed.
If d1-18 = 3
7 preset speed steps (defined in the parameters d1-02 to d1-08) can be selected using 3 binary coded digital
inputs. The Up/Down command starts the inverter. It is stopped when the Up/Down command is removed or
when no speed is selected (all D/Is off).
Related Parameters
Parameter
No.
d1-01 to
Multi-Step speed 1 to 8 reference value
d1-08
Multi-function Digital Input Settings (H1-01 to H1-05) (Example)
Parameter
Terminal
Number
S4
H1-02
S5
H1-03
S6
H1-04
Factory
Name
Setting
Factory
Name
Setting
0.00 Hz
0.00%
Set Value
3
Multi-step speed command 1
4
Multi-step speed command 2
5
Multi-step speed command 3
Control Methods
Change
Open
during
V/f
Loop
Operation
Vector
1
No
Q
Q
Control Methods
Change
Open
during
V/f
Loop
Operation
Vector
A
A
Yes
-
-
Details
Closed
Closed
Loop
Loop
Vector
Vector
(PM)
Q
Q
Closed
Closed
Loop
Loop
Vector
6
Vector
(PM)
A
-
-
A
5
6-