Monitor Data
The following table shows the monitor data. Monitor data can only be read.
Register Address.
0010H
0011H
0012H
0013H
6
0014H
0015H
88
6-
Inverter status signal
Bit 0
During run
Bit 1
Zero speed
Bit 2
During reverse operation
Bit 3
Reset signal active
Bit 4
During speed agree
Bit 5
Inverter ready
Bit 6
Minor fault
Bit 7
Major fault
Bits 8 to D
Not used
Bit E
ComRef status
Bit F
ComCtrl status
Operator status
Bit 0
During OPE alarm
Bit 1
During fault
Bit 2
Operator in programming mode
Bit 3
0: Digital operator attached
Bit 4 to F
Not used
OPE Fault Number
Not used
Fault Content 1
Bit 0
PUF, DC bus fuse blown
Bit 1
UV1
Bit 2
UV2
Bit 3
UV3
Bit 4
Not used
Bit 5
GF, Ground fault
Bit 6
OC, Over current
Bit 7
OV, DC bus over voltage
Bit 8
OH, Inverter heatsink overheat pre-alarm
Bit 9
OH1, Inverter heatsink overheat
Bit A
OL1, Motor overload
Bit B
OL2, Inverter overload
Bit C
OL3, Overtorque detection 1
Bit D
OL4, Overtorque detection 2
Bit E
RR, Internal braking transistor fault
Bit F
RH, Inverter mounted braking resistor overheat
Fault Content 2
Bit 0
EF3, External fault set on terminal S3
Bit 1
EF4, External fault set on terminal S4
Bit 2
EF5, External fault set on terminal S5
Bit 3
EF6, External fault set on terminal S6
Bit 4
EF7, External fault set on terminal S7
Bit 5
Not used
Bit 6
Not used
Bit 7
OS, Overspeed detected
Bit 8
DEV, Speed deviation detected
Bit 9
PGO, PG disconnected
Bit A
PF, Input phase loss
Bit B
LF, Output open phase
Bit C
OH3, Motor overheat pre-alarm (PTC analog input)
Bit D
OPR, Digital operator disconnected
Bit E
ERR, EPROM error
Bit F
Not used
Contents
1: PC connected