The falling edge of the Inspection Speed command or UP/DOWN commands triggers the contactor open com-
mand, the motor brake close command and the base block.
Speed
Hardware BB
Up/Down (D/I)
Inspection Speed
Internal RUN
MC closed (D/O)
Brake opened (D/O)
S3-03 > 0 sec., Stop with deceleration ramp
The inverter stops when the Inspection Speed command or the Up/Down command is removed. In this case:
The output frequency is reduced using the deceleration time set in S3-03.
When the minimum frequency is reached the brake open signal is removed immediately and the contactor
control output is removed immediately
The inverter output is cut after the brake open command removal.
The falling edge of the Inspection Speed command or UP/DOWN commands triggers the deceleration.
Speed
6
Hardware BB
Up/Down (D/I)
Inspection Speed
Internal RUN
MC closed (D/O)
Brake opened (D/O)
INFO
12
6-
Inspection RUN
(Stop by Up/Down signal removal)
DC Injection/
zero servo
Inspection RUN
(Stop by Up/Down signal removal)
DC Injection/
zero servo
During inspection run the carrier frequency is reduced to 2 kHz.
Inspection RUN
(Stop by Inspection Speed signal removal)
DC Injection/
zero servo
Speed
Hardware BB
Up/Down (D/I)
Inspection Speed
Internal RUN
MC closed (D/O)
Brake opened (D/O)
Inspection RUN
(Stop by Inspection Speed signal removal)
DC Injection/
zero servo
Speed
Hardware BB
Up/Down (D/I)
Inspection Speed
Internal RUN
MC closed (D/O)
Brake opened (D/O)