Operation Mode Selection; V/F Characteristic Setting - Omron SYSDRIVE 3G3XV-EV2 Series Operation Manual

Table of Contents

Advertisement

Description of Functions and Constants
2-8-2

Operation Mode Selection

Start/Stop Procedure
Stop Procedure
Reverse Rotation
Prevention
Note
2-8-3

V/f Characteristic Setting

Constant no. 00 value
8
9
Item name
Start/stop procedure
Reverse rotation prevention
Control input can be selected from the Digital Operator or the ter-
minal strip.
No. 1 = xx 11 (x means 1 or 0.)
0: Frequency command from external terminal
1: Frequency command from the operator
0: Start/stop control from external terminal
1: Start/stop control by the operator
Stopping Mode can be selected according to the application
No. 1 = x0xx
0: Ramp to stop
1: Coasting to a stop
Prevents accidental selection of reverse rotation.
No. 20 = xx01
0: Reverse rotation is possible.
1: Reverse rotation is impossible.
0: STOP Key of Digital Operator effective.
1: STOP Key of Digital Operator ineffective.
When controlling from the Digital Operator, the STOP Key is al-
ways effective regardless of the 2
Item name
Output Voltage Limiter Selection
Max. Output Frequency
Max. Voltage
Max. Voltage Output Frequency
Intermediate Output Frequency
Intermediate Output Frequency Voltage No. 06
Min. Output Frequency
Min. Output Frequency Voltage
Function
Initializes all control constants. Terminal functions
are returned to the initial factory settings.
Initializes all control constants. Terminal functions
are 3-wire sequence. For details, refer to 2-8-14
Multifunction Contact Input Function Selection .
Constant to be set
No. 01
No. 20
nd
digit setting of constant no. 20.
Constant
No. 01
No. 02
No. 03
No. 04
No. 05
No. 07
No. 08
Section 2-8
Factory preset
0011
0000
Factory preset
0011
60.0 Hz
200.0 V (See note 1.)
60.0 Hz
1.5 Hz
12.0 V (See note 1.)
1.5 Hz
12.0 V (See note 1.)
45