User Parameters Available in Quick Programming Mode

The minimum user parameters required for Inverter operation can be monitored and set in quick programming
mode. The user parameters displayed in quick programming mode are listed in the following table. These, and
all other user parameters, are also displayed in advanced programming mode.
Name
Param-
eter
Num-
Display
ber
Parameter access
level
A1-01
Access Level
Control method
selection
A1-02
Control Method
5
Acceleration time 1 Sets the acceleration time to accelerate
C1-01
Accel Time 1
Deceleration time 1 Sets the deceleration time to decelerate
C1-02
Decel Time 1
S-curve character-
istic time at accel-
C2-01
eration start
S-Crv Acc @ Start
S-curve character-
istic time at accel-
C2-02
eration end
S-Crv Acc @ End
S-curve character-
istic time at decel-
C2-03
eration start
S-Crv Dec @ Start
S-curve character-
istic time at decel-
C2-04
eration end
S-Crv Dec @ End
S-curve Character-
istic time below
C2-05
leveling speed
Scurve @ leveling
ASR proportional
(P) gain 1
C5-01
ASR P Gain 1
ASR integral time
1
C5-02
ASR I Time 1
4
5-
Description
Used to set the parameter access level
(set/read.)
0: Monitoring only (Monitoring drive
mode and setting A1-01 and A1-04.)
1: Used to select user parameters (Only
parameters set in A2-01 to A2-32 can
be read and set.)
2: Advanced
(Parameters can be read and set in
both, quick programming mode (Q)
and advanced programming mode
(A).)
Sets the control method for the Inverter.
0: V/f control
2: Open-Loop Vector control
3: Closed Loop Vector control
6: Closed Loop Vector for PM motors
from 0 Hz to the maximum output fre-
quency.
from the maximum output frequency to
0 Hz.
When the S-curve characteristic time is
set, the accel/decel times will increase
by only half of the S-curve characteris-
tic times at start and end.
Set the proportional gain 1 and the inte-
gral time 1 of the speed control loop
(ASR) for the minimum frequency.
The settings becomes active for acceler-
ation only.
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 2
2
Yes
Yes
0 to 6
0
No
Yes
0.0 to
600.00
1.50 s
Yes
Yes
*1
0.00 to
0.50 s
No
Yes
2.50
0.00 to
0.50 s
No
Yes
2.50
0.00 to
0.50 s
No
Yes
2.50
0.00 to
0.50 s
No
Yes
2.50
0.00 to
0.50 s
No
Yes
2.50
0.00 to
i
Yes
-
300.00
0.000
to
i
Yes
-
10.000
Control Methods
MEMO
Closed
BUS
Open
Closed
Loop
Regis-
Loop
Loop
Vector
ter
Vector
Vector
(PM)
Yes
Yes
Yes
101H
Yes
Yes
Yes
102H
200H
Yes
Yes
Yes
201H
Yes
Yes
Yes
20BH
Yes
Yes
Yes
20CH
Yes
Yes
Yes
20DH
Yes
Yes
Yes
20EH
Yes
Yes
Yes
232H
40.00
-
-
21BH
-
12.00
0.500
-
s
-
21CH
-
0.300 s