Emergency Stop

If a digital input terminal (H1-
inverter in the case of emergency. In this case the emergency stop deceleration time set in C1-09 is used. If the
emergency stop is input with an NO contact, set the multi-function input terminal (H1-
gency stop is input with an NC contact, set the multi-function input terminal (H1-
After the emergency stop command has been input, the operation cannot be restarted until the Inverter has
stopped. To cancel the emergency stop, turn OFF the run command and emergency stop command.
Related parameters
Parameter
No.
C1-09
Multi-function Digital Inputs (H1-01 to H1-05)
Set
Value
15
Emergency Stop, NO contact
17
Emergency Stop, NC contact
6
10
6-
) is set to 15 or 17 (emergency stop), this input can be used to fast stop the
Name
Emergency stop time
Function
Control Methods
Change
Factory
during
Setting
V/f
Operation
Vector
1.50 s
No
A
Control Methods
V/f
Yes
Yes
) to 15, if the emer-
) to 17.
Closed
Open
Closed
Loop
Loop
Loop
Vector
Vector
(PM)
A
A
A
Closed
Open
Closed
Loop
Loop
Loop
Vector
Vector
Vector
(PM)
Yes
Yes
Yes
Yes
Yes
Yes