Scaling upper limit

Scaling lower limit

Decimal point

• This parameter can be used only when voltage input or current input is selected
as the input type.
• When voltage input or current input is selected as the input type, scaling is car-
Function
ried out. Set the scaling upper limit in the "scaling upper limit" parameter and
the scaling lower limit in the "scaling lower limit" parameter.
• The "decimal point" parameter specifies the decimal point position of parameters
(set point, etc.) whose unit is set to EU (Engineering Unit).
• Scaling upper limit, Scaling lower limit
Parameter
Scaling upper limit
Comment
Scaling lower limit
• Decimal point : default : 0
Set Value
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameter
See
"Input type" (setup mode)

Parameter initialize

• Returns parameter settings to their defaults. However, note that the following
parameters are not affected by execution of this parameter:
"input type", "scaling upper limit", "scaling lower limit", "decimal point" and
Function
"_C/_F selection".
• When this parameter is selected, [
parameters, press the
Example
of use
Scaling lower limit +1 to 9999
-1999 to scaling upper limit -1
Setting
0
0 digits past decimal point
1
1 digit past decimal point
2
2 digits past decimal point
3
3 digits past decimal point
key to specify [
Conditions of Use
The input type must be set to analog
input (voltage or current input).
Setting Range
Example
1234
123.4
12.34
1.234
] ("no") is first displayed. To initialize
] ("yes").
Setup Mode
Unit
Default
EU
100
EU
0
5--27