Setting Example
1 second min.
1 second min.
1 second min.
All of the above settings in this example are factory settings. In this ex-
ample, let's check the parameter settings.
In this example, the parameters are set as follows:
"control output 1 assignment"
"auxiliary output 1 assignment" = "alarm output 2"

"direct/reverse operation"

"control period"

(1) Select the menu display, and select "
or
keys. For details on selecting the menu display, see page
1-10.
(2) Press the
key for one second minimum to enter the setup
mode. The top parameter in the setup mode "
displayed.
(3) Press the
key until [
parameter) is displayed. Default is [
(4) As the setting in this example is to be left as it is, press the
twice. The display changes to [
ment" parameter). Default is [
(5) As the setting in this example is to be left as it is, press the
until [
] ("direct/reverse operation" parameter) is displayed.
Default is [
].
(6) As the setting in this example is to be left as it is, press the
keys to select "
the menu display, see page 1-7.
(7) Press the
key for one second minimum to enter the level 1
mode. The top parameter in the level 1 mode "
band" is displayed.
(8) Press the
key until [
is displayed. Default is "20". As the setting in this example is to be
left as its is, quit key operation.
3.3 Setting Output Specifications
= "control output (heat)"
= "reverse operation"
= "20 secs"
: setup mode" using the
] ("control output 1 assignment"
].
] ("auxiliary output 1 assign-
].
: level 1 mode". For details on selecting
] ("control period (heat)" parameter)
: input type" is
key
key
or
: Proportional
3--9