Set point upper limit
Set point lower limit
• Limits the upper and lower limits when the SP is set. The SP can be set within the
range defined by the upper and lower limit set values of the "set point upper
limit" and "set point lower limit " parameters. Note that as these parameters are
Function
reset, the SP of existing settings that are out of the range are forcibly changed to
one of the upper or lower limit values.
• When the temperature input type and temperature unit have been changed, the
set point upper limit and set point lower limit are forcibly changed to the upper
and lower limits of the sensor.
• During temperature input, the decimal point position is dependent on the cur-
rently selected sensor, and during analog input on the results of scaling.
Set point upper limit
Set point lower limit
Setting
During temperature input, the range becomes the range of use of the selected sen-
sor instead of the range defined by the scaling upper and lower limit values.
F Related description
4.2 Operating Condition Restrictions (page 4-7)
F Related parameter
See
"Input type" "Scaling upper limit" "Scaling lower limit" "Decimal point" (setup
mode)
PID/ON/OFF
• Selects advanced PID control or ON/OFF control.
Function
"
Setting
F Related description
4.1 Selecting the Control Method/ON/OFF control (page 4-5)
F Related parameters
See
"Hysteresis (heat)" "Hysteresis (cool)" (level 1 mode)
E5AK-TAA2
Model
Parameter
Set point lower limit +1 to scaling upper limit
Scaling lower limit to set point upper limit -1
Setting Range
" :Advance PID/ "
Expansion Mode
Setting Range
Conditions of Use
The control must be standard control or
heating and cooling control.
Default
" :ON/OFF
Unit
Default
EU
1300
EU
-200
5--39