CHAPTER 7 CALIBRATION
From previous page
Short terminal
Nos.11 to 13
7--8
(5) Press the
key to display [
the 6-dial to 10Ω. When the value on the No.2 display has stabilized
(changes of several digits max.), press the
store the calibration data.
(6) Press the
key to display [
terminal Nos.11 to 13. When the value on the No.2 display has sta-
bilized (changes of several digits max.), press the
rarily store the calibration data.
(7) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (11). Press the
display changes to [
(8) Set the output to 20 mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "20 mA".
(9) Press the
key. The display changes to [
tion display).
(10) Set the output to 4 mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "4 mA".
(11) Press the
key until the display changes to the data store dis-
play.
Press the
key. The No.2 display changes to [
seconds later the calibration data is stored to internal memory. If
you press the
ibration data is disabled.
(12) This completes calibration of the platinum resistance thermometer.
Press the
key to return the display to [
] (10Ω calibration display). Set
] (0Ω calibration display). Short
] (20 mA calibration display).
or
or
key when the No.2 display reads [
key to temporarily
key to tempo-
key. The
keys while monitoring
] (4 mA calibra-
keys while monitoring
], and two
], the cal-
].