4.7 Setting Running Conditions

J Operation at
power ON
• You can select from one of the following operations at power ON:
Continue, Reset, Run, Manual
• If you select "Continue," operation is started from the state that was
active when power was interrupted.
• If you select "Reset," the controller is reset.
• If you select "Run," normal program operation is started.
• If you select "Manual," the controller enters the manual mode.
• The following table shows the relationship between operation at pow-
er ON and the operation details that are stored to memory when a
power interruption occurs.
Pattern No.
Step No.
Pattern elapsing time
Pattern execution count
Hold status
Auto/Manual
Run/Reset
MV at reset *1
Manual MV *2
*1 During auto mode at power interruption on a standard type controller
*2 During manual mode at power interruption on a standard type controller
• Set the desired operation in the "operation at power ON" parameter
(expansion mode). Default is "

4.7 Setting Running Conditions

Continue
Reset
f
f
-
f
-
f
-
f
-
f
f
f
-
f
-
f
f
f
: Continue".
Run
Manual
f
f
-
f
-
f
-
f
-
f
-
f
-
f
-
f
f
f
4--19