Omron E5AK PROGRAMMABLE TYPE User Manual page 173

Digital controller (programmable type)
Hide thumbs Also See for E5AK PROGRAMMABLE TYPE:
Table of Contents

Advertisement

From previous page
F Calibration:
0 to 10V
(8) Press the
key until the display changes to the data store dis-
play.
Press the
key. The No.2 display changes to [
seconds later the calibration data is stored to internal memory. If
you press the [
calibration data is disabled.
(9) This completes calibration of the voltage input (0 to 5 V , 1 to 5 V).
Press the
key to return the display to [
This example describes how to calibrate a platinum resistance ther-
mometer when the transfer output function is supported. If the transfer
output function is not supported, skips steps (4) to (7).
(1) When [
] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the
key. The display changes to [
display). Set the STV output to 10 V . When the value on the No.2
display has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(3) Press the
key. The display changes to [
display). Set the STV output to 0 V . When the value on the No.2
display has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(4) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (8). Press the
display changes to [
(5) Set the output to 20 mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "20 mA".
(6) Press the
key. The display changes to [
tion display).
(7) Set the output to 4 mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "4 mA".
(8) Press the
key until the display changes to the data store dis-
play.
Press the
key. The No.2 display changes to [
seconds later the calibration data is stored to internal memory. If
you press the
ibration data is disabled.
(9) This completes calibration of the voltage input (0 to 10 V). Press
the
key to return the display to [
7.5 Calibrating Voltage Input
] key when the No.2 display reads [
] (20 mA calibration display).
or
or
key when the No.2 display reads [
], and two
], the
].
] (10 V calibration
] (0 V calibration
key. The
keys while monitoring
] (4 mA calibra-
keys while monitoring
], and two
], the cal-
].
7--11