CHAPTER 5 PARAMETERS
Level 2 Mode
LBA detection time
• This parameter is automatically set by AT execution.
• The LBA is output if the change width of the process value falls below 0.2 %full-
scale of the time preset to this parameter when the manipulated variable is set in
Function
the "MV upper limit" or "MV lower limit" parameters.
• The LBA function is disabled when this parameter is set to "0".
Setting
F Related description
4.10 LBA (page 4-20)
8.3 How to Use Error Output (page 8-5)
See
F Related parameters
"AT Execute/Cancel" (level 1 mode)
"Control output 1 assignment" "Control output 2 assignment" "Auxiliary output
1 assignment" "Auxiliary output 2 assignment" (setup mode)
MV at reset
MV at PV error
• The "MV at reset" parameter sets the manipulated variable when operation has
stopped on a standard type controller. On a position-proportional type controller,
this parameter sets the action (close/hold/open) when operation has stopped.
Function
• The "MV at PV error" parameter sets the manipulated variable when an input
error occurs. On a position-proportional type controller, this parameter sets the
action (close/hold/open) when an input error occurs.
• Standard type
Standard
Setting
Heating and cooling
The manipulated variable at the cooling side during heating and cooling control is
expressed as a negative value.
• Position-proportional type
"
F Related description
MV at reset
MV at PV error
See
5--26
Unit
Setting Range
0 to 9999
Second
Control Method
Setting Range
": Hold/"
": Open/"
: 3.7 Starting and Stopping Operation (page 3-21)
: 8.2 How to Use the Error Display (page 8-3)
Conditions of Use
The LBA (Loop Break Alarm) function
must be assigned as an output.
Default
0
Conditions of Use
Advanced PID control.
Unit
Setting Range
-5.0 to 105.0
%
-105.0 to 105.0
%
Unit
": Close
None
Default
0.0
0.0
Default