CHAPTER 5 PARAMETERS
Program Mode
Pattern execution count
• Repeatedly executes the current pattern for the preset number of times.
• The count during pattern execution can be monitored in the "pattern execution
count monitor" (level 0 mode).
Function
Setting
F Related description
4.4 Program Operation/Pattern operation (page 4-13)
F Related parameters
See
All parameters in the program mode
Alarm value 1
Alarm value 2
Alarm value 3
• This parameter is used for monitoring or setting the alarm values of alarm out-
puts 1 to 3.
• During temperature input, the decimal point position is dependent on the cur-
Function
rently selected sensor, and during analog input on the results of scaling.
Setting
F Related description
3.4Setting Alarm Type (page 3-10)
3.5Setting Patterns/Alarm value (page 3-16)
See
F Related parameters
"Input type" "Scaling upper limit" "Scaling lower limit" "Decimal point" "Con-
trol output 1 assignment" "Control output 2 assignment" "Auxiliary output 1
assignment" "Auxiliary output 2 assignment" "Alarm 1 type" "Alarm 2 type"
"Alarm 3 type" "Alarm 1 open in alarm" "Alarm 2 open in alarm" "Alarm 3 open
in alarm" (setup mode)
"Alarm 1 hysteresis" "Alarm 2 hysteresis" "Alarm 3 hysteresis" (level 2 mode)
5--14
Setting Range
0 to 9999
0: The pattern is not executed
Setting Range
-1999 to 9999
Unit
Time
Conditions of Use
Alarms must be assigned as outputs.
For example, if alarm outputs 1 and 2
only are assigned as outputs, the "alarm
value 3" parameter cannot be used.
Unit
EU
Default
1
Default
0