CHAPTER 7 CALIBRATION

7.5 Calibrating Voltage Input

F Preparation
F Calibration:
0 to 5V, 1 to 5V
Cont'd on next page
7--10
100-240VAC
(24VAC/DC)
10
SOURCE
9
8
7
6
5
4
3
2
1
• In the above figure, STV refers to a standard DC current/voltage
source, and DMM refers to a precision digital multimeter. However,
note that the DMM is required only when the transfer output func-
tion is supported.
This example describes how to calibrate a platinum resistance ther-
mometer when the transfer output function is supported. If the transfer
output function is not supported, skips steps (4) to (7).
(1) When [
] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) Press the
key. The display changes to [
display). Set the STV output to 5 V . When the value on the No.2
display has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(3) Press the
key. The display changes to [
display). Set the STV output to 0 V . When the value on the No.2
display has stabilized (changes of several digits max.), press the
key to temporarily store the calibration data.
(4) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (8). Press the
display changes to [
(5) Set the output to 20 mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "20 mA".
(6) Press the
key. The display changes to [
tion display).
(7) Set the output to 4 mA by the
the voltage on the digital multimeter. In the example on the left,
the display indicates that the value two digits smaller than before
calibration is "4 mA".
30
20
31 32
29
19
28
18
27
17
26
16
25
15
24
14
23
13
22
12
33
21
11
DMM
] (20 mA calibration display).
or
or
keys while monitoring
+
STV
-
] (5 V calibration
] (0 V calibration
key. The
keys while monitoring
] (4 mA calibra-