Omron E5AK PROGRAMMABLE TYPE User Manual page 151

Digital controller (programmable type)
Hide thumbs Also See for E5AK PROGRAMMABLE TYPE:
Table of Contents

Advertisement

Parameter No.
57
Input type
59
Scaling upper limit
58
Scaling lower limit
60
Decimal point
30
_C/_F selection
61
Control output 1 assignment
62
Control output 2 assignment
63
Auxiliary output 1 assignment
64
Auxiliary output 2 assignment
65
Alarm 1 type
66
Alarm 1 open in alarm
67
Alarm 2 type
68
Alarm 2 open in alarm
69
Alarm 3 type
70
Alarm 3 open in alarm
71
Direct/Reverse operation
28
Set point upper limit *1
27
Set point lower limit *1
72
PID / ON/OFF
35
α
85
AT calculated gain
36
Automatic return of display mode
93
AT hysteresis
55
LBA detection width
77
Event input assignment 3
78
Event input assignment 4
79
Transfer output type
81
Transfer output upper limit
80
Transfer output lower limit
82
HBA latch
89
Travel time
38
PV dead band
*7 See page 5-31.
*8 0: Control output (heat), 1: Control output (cool), 2 to 4: Alarms 1 to 3, 5: HBA, 6: LBA, 7 and 8: Errors 1 to 2, 10 to 11: Time
signal 1 to 2, 12: Program end, 13: Stage output
*9 See page 5-37.
*10 During temperature input, the range becomes the range of use of the selected sensor instead of the scaling upper/lower limit
values.
*11 -1: No specification, 0: Run/Reset, 1: Remote/Local, 2: Auto/Manual, 4: Hold/Hold cancel, 5: Advance, 6 to 8: Pattern select 0 to 2
*12 The following table shows the output ranges of the transfer output lower and upper limits.
Transfer Output Type
0: Present SP
2: Process value
3: Manipulated variable (heat)
4: Manipulated variable (cool)
5: Valve opening
Parameter
Transfer Output Lower Limit to
Transfer Output Upper Limit
-5.0 to 105.0% (standard control),
0.0 to 105.0% (heating and cooling control)
6.4 Commands and Responses
Data Setting Range
0 to 21
Scaling lower limit +1 to 9999
-1999 to scaling upper limit -1
0 to 3
0: _C, 1: _F
0 to 6, 10 to 13
0 to 6, 10 to 13
2 to 8, 10 to 13
2 to 8, 10 to 13
1 to 11
0: Closed in alarm, 1: Open in alarm
1 to 11
0: Closed in alarm, 1: Open in alarm
1 to 11
0: Closed in alarm, 1: Open in alarm
0: Reverse operation, 1: Direct operation
Set point lower limit +1 to scaling upper limit
Scaling lower limit to Set point upper limit -1
0: Advanced PID, 1: ON/OFF
0.00 to 1.00
0.1 to 10.0
0 to 99
0.1 to 9.9
0.0 to 999.9
-1 to 2, 4 to 8
-1 to 2, 4 to 8
0 to 5
0: OFF, 1: ON
1 to 999
0 to 9999
-1999 to 9999
-1999 to 9999
0.0 to 105.0%
-10.0 to 110.0%
Mode
*7
*8
*8
*8
Set up
Set up
*8
*9
*9
*9
Expansion
Expansion
*11
*11
*12
*12
Option
Option
*12
6--9