Nortel Communication Server 1000 Series Manual page 87

Fiber remote multi-ipe interface fundamentals
Table of Contents

Advertisement

31). Also, refer to
Interface unit cable connection diagram" (page 154)
diagram.
Label one fiber XMIT A and its pair RCV A at one end of the link. Label
these two fibers at the other end of the link with the opposite label; that is,
the XMIT A at one end should be labeled RCV A at the other end of the
link and the RCV A at one end should be labeled XMIT A at the other end
of the link. Repeat the same procedure for the redundant link with XMIT B
and RCV B. For an illustration of the link fibers labelling, refer to
"Fiber-optic link" (page
To connect the fiber-optic link to the Fiber Remote Multi-IPE Interface at
the Remote IPE site, follow the steps in
fiber-optic link to the Fiber Remote Multi-IPE Interface at the Remote IPE
site" (page
Procedure 26
Connecting the fiber-optic link to the Fiber Remote Multi-IPE Interface at the
Remote IPE site
Step
1
2
3
4
Copyright © 2007-2009 Nortel Networks
.
Figure 17 "Remote site single Fiber Remote Multi-IPE
Note:
Label optical fibers in the fiber-optic cable next to the ST optical
connectors. Label one fiber XMIT A and its pair RCV A at one end of
the link. Label these two fibers at the other end of the link with opposite
labels; that is, the XMIT A at one end should be labeled RCV A at
the other end of the link and the RCV A at one end should be labeled
XMIT A at the other end of the link. Repeat the same procedure for the
redundant link with XMIT B and RCV B. At the cross-connect, typical
designation is: Pos A for receive fiber and Pos B for the transmit fiber.
For illustration of the link fibers labelling, refer to
link" (page 45)
in the Product description section of this document.
45).
87).
Action
Identify the link ST optical connectors labeled XMIT A and RCV
A for a single link, or labeled XMIT A, RCV A, XMIT B, and RCV
B for a redundant link.
Plug the link ST optical connector labeled XMIT A into the Fiber
Remote Multi-IPE Interface faceplate ST optical connector
labeled XMIT A.
Plug the link ST optical connector labeled RCV A into the Fiber
Remote Multi-IPE Interface faceplate ST optical connector
labeled RCV A.
Repeat steps 2 and 3 for the XMIT B and RCV B if there is a
redundant link.
Nortel Communication Server 1000
Fiber Remote Multi-IPE Interface Fundamentals
NN43021-556 03.01
11 May 2009
Remote IPE installation 87
for the connection
Figure 6 "Fiber-optic
Procedure 26 "Connecting the