The connector provides:
•
•
The two external alarm inputs (alarm inputs #1 and #2), when activated,
are transmitted from a remote Fiber Remote Multi-IPE Interface over the
fiber-optic link to the local Fiber Remote Multi-IPE Interface to activate two
out of three external alarm outputs (alarm outputs #1 and #2) on the local
Fiber Remote Multi-IPE Interface unit. At the local site, the alarm output #3
is activated when the fiber-optic link detects an alarm condition.
The single alarm output at the remote Fiber Remote Multi-IPE Interface
will be activated if an external alarm is activated or if the fiber-optic link
detects an alarm condition.
Figure 5 "External alarm inputs and outputs" (page 29)
external alarm inputs at the remote Fiber Remote Multi-IPE Interface
location and the corresponding alarm outputs at the local Fiber Remote
Multi-IPE Interface.
Figure 5
External alarm inputs and outputs
LED indicators. The LED indicators are located on the faceplate of each
Fiber Remote Multi-IPE Interface unit. These LEDs are:
Copyright © 2007-2009 Nortel Networks
.
three external alarm outputs on each local Fiber Remote Multi-IPE
Interface unit
two external alarm inputs and one external alarm output on each
remote Fiber Remote Multi-IPE Interface unit
Nortel Communication Server 1000
Fiber Remote Multi-IPE Interface Fundamentals
NN43021-556 03.01
11 May 2009
System description 29
illustrates the