Siemens SIMATIC NET SCALANCE SC-600 Configuration Manual page 350

Industrial ethernet security web based management (wbm)
Hide thumbs Also See for SIMATIC NET SCALANCE SC-600:
Table of Contents

Advertisement

Upkeep and maintenance
5.2 Firmware update using WBM not possible
Solution
You can then also transfer firmware to the device using TFTP.
Follow the steps below to load new firmware using TFTP:
1. When starting up press the SET button.
2. Hold down the button until the red fault LED (F) starts to flash after approximately 3
seconds.
Note
If you hold down the SET button for approximately 10 seconds, the device is reset to
its factory settings.
3. Now release the button. The bootloader waits in this state for a new firmware file that
you can download by TFTP.
Note
If you want to exit the bootloader without making changes, press the SET button
briefly. The device restarts with the loaded configuration.
4. Connect a PC to the device over the Ethernet interface (P0.1 - P0.6).
5. Open a DOS box, change to the directory where the new firmware file is located and
then execute the command "tftp -i <ip address> PUT <firmware>". As an alternative,
you can use a different TFTP client.
If you are not sure that the IP address is correct, you can check this, for example with
SINEC PNI.
Note
Using TFTP
If you want to access TFTP in Windows 7, make sure that the corresponding Windows
function is enabled in the operating system.
Result
The firmware is transferred to the device.
Note
Please note that the transfer of the firmware can take several minutes. During the
transmission, the red error LED (F) flashes.
Once the firmware has been transferred completely to the device, the device is restarted
automatically.
350
SCALANCE SC-600 Web Based Management (WBM)
Configuration Manual, 10/2021, C79000-G8976-C475-03