4.5.4
Ring redundancy (SC6x6-2C)
4.5.4.1
Ring
Rules for ring redundancy
Factory settings
• The factory setting defines ports P0.1 and P0.2 as ring ports.
Enabling redundancy
You can enable ring redundancy as follows:
• using the WBM
• using the CLI
Configuration of ring redundancy
• Ring Redundancy
If you enable the "Ring Redundancy" check box, you turn ring redundancy on. The
Ring Ports set on this page are used.
• Ring redundancy mode
Here, you set the mode of the ring redundancy.
The following modes are available:
– MRP Client
– HRP Client
• Ring ports
Here, you set the ports to be used as ring ports in ring redundancy.
SCALANCE SC-600 Web Based Management (WBM)
Configuration Manual, 10/2021, C79000-G8976-C475-03
The device adopts the role of MRP client.
The device adopts the role of HRP client.
Configuring with Web Based Management
4.5 "Layer 2" menu