Appendix A: Integration with Allen Bradley PLC
4. On the Connection tab:
NOTE:
NOTE: An asterisk appears after the tab heading if unsaved changes are present. Click the Apply button to
NOTE:
save changes without exiting this screen.
a. Enter a Requested Packet Interval (RPI) value.
NOTE:
NOTE: Graco recommends a value of 30 ms or greater.
NOTE:
b. If desired, select the available checkboxes.
c. Click the OK button to save all changes and exit this screen.
Table
Table
Table 7 7 7 Potential
Potential Configuration
Potential
Configuration Problems
Configuration
Error
Error
Error
Connection Request Error — Invalid Input
Application Path
Connection Request Error — Invalid Output
Application Path
Connection Request Error — Invalid Input
Size
Connection Request Error — Invalid Output
Size
Module Configuration Rejected — Format
Error
114
Problems
Problems
Description
Description
Description
This error, which also triggers an I/O Fault on the PLC, is caused by
an invalid number being entered for the Input:
parameter. The correct value for this parameter is "100".
This error, which also triggers an I/O Fault on the PLC, is caused by
an invalid number being entered for the Output:
parameter. The correct value for this parameter is "150".
This error, which also triggers an I/O Fault on the PLC, is caused by
an invalid number being entered for the Input:
correct value for this parameter is "62".
This error, which also triggers an I/O Fault on the PLC, is caused by
an invalid number being entered for the Output:
correct value for this parameter is "30".
This error, which also triggers an I/O Fault on the PLC, is caused
by an invalid number being entered for the Configuration:
parameter. Because there are no configuration registers associated
with the module, the correct value for this parameter is "0".
Input: Assembly
Assembly Instance
Instance
Input:
Assembly
Instance
Output: Assembly
Output:
Assembly Instance
Assembly
Instance
Instance
Input: Size
Input:
Size parameter. The
Size
Output: Size
Size parameter. The
Output:
Size
Configuration: Size
Configuration:
Size
Size
3A4486D