SPECIFICATIONS

3.4.12 Warning output flag (Un\G48)

(1) When the digital input value falls outside the CH
lower limit value (Un\G86 to Un\G97) range, the bit corresponding to each channel
turns to "1".
(2) Whether the warning is the upper or lower limit value warning can be checked on each
channel.
(3) If the warning is detected on any of the channels enabled for conversion, the warning
output signal (XE) turns ON.
(4) Turning ON the operating condition setting request (Y9) or warning output clear
request (YE) clears the warning output flag.
Un\G48
b12 to b15 information is fixed at 0
(5) Refer to Section 3.2.3 for details of warning output function.

3.4.13 Scaling enable/disable setting (Un\G53)

(1) Set whether to enable or disable the scaling on each channel.
(2) To validate the settings, ON/OFF of the Operating condition setting request (Y9) is
required. (Refer to Section 3.3.2.)
(3) The default setting is all-channel scaling disable.
Un\G53
(4) Refer to Section 3.2.5 for details of warning output function.
b15 b14 b13 b12 b11 b10
CH6 CH6 CH5 CH5
lower
upper
0
0
0
0
limit
limit
value
value
b15 b14 b13 b12 b11 b10
0
0
0
0
0
b6 to b15 information is fixed at 0
warning output upper limit value/
b9
b8
b7
b6
b5
CH4 CH4 CH3 CH3
lower
upper
lower
upper
lower
limit
limit
limit
limit
limit
value
value
value
value
value
b9
b8
b7
b6
b5
CH
0
0
0
0
0
6
3.4 Buffer Memory
3.4.12 Warning output flag (Un\G48)
b4
b3
b2
b1
b0
CH2 CH2 CH1 CH1
upper
lower
upper
lower
upper
limit
limit
limit
limit
limit
value
value
value
value
value
1: Warning output
0: Normal
b4
b3
b2
b1
b0
CH
CH
CH
CH
CH
5
4
3
2
1
1: Scaling disable
0: Scaling enable
3
1
2
3
4
5
6
7
8
- 35