3
SPECIFICATIONS
3
- 8
3.1 Performance Specifications
3.1.2 I/O conversion characteristics
(1) Set within the digital input range and analog output range for each output
range.
If these ranges are exceeded, the maximum resolution and accuracy may not
fall within the performance specifications. (Avoid using the dotted line area
shown in Figures 3.3 and 3.4.)
(2) Set the offset/gain values for the user range setting 1 *1 within a range in
which the following conditions are satisfied.
(a) Setting range is from 0 to 22 mA
(b) { (Gain value) - (Offset value) } > A
<Value of A>
Normal resolution mode
6.0mA
High resolution mode
11.5mA

Advertisement