Range Reference Table

The range reference tables are given below.
(1) Reference table for offset/gain values of industrial shipment settings
Address (Decimal)
CH1
CH2
CH3
CH4
202
204
206
208
203
205
207
209
(2) Reference table for user range settings offset/gain values (Un\G214 to
7
- 35
7.4 Range Reference Table
(Un\G202 to 213)
The reference values change depending on the setting of the pass data classification
setting (Un\G200).
Description
CH5
CH6
Industrial shipment
210
212
settings offset value
Industrial shipment
211
213
settings gain value
225)
Offset/gain value
0mA
User range
4mA
setting 1
20mA
-10V
User range
0V
setting 2
10V
0V
User range
1V
setting 3
5V
[Example]
When using User range setting 3 in channel 1 and setting 1V to the offset value and
5V to the gain value, the following values are stored in the User range setting offset/
gain value areas.
• CH1 user range settings offset value (Un\G214): Approx. 9427
• CH1 user range settings gain value (Un\G215): Approx. E4C8
Pass data classification setting
User range setting 1
User range setting 2
User range setting 3
User range setting 1
User range setting 2
User range setting 3
Reference value
Approx. 7FFF
Approx. 6DB9
Approx. 24A0
Approx. 1B36
Approx. 7FFF
Approx. E4C8
Approx. 7FFF
Approx. 9427
Approx. E4C8
Reference value
(Hexadecimal)
0mA
Approx. 7FFF
H
0V
Approx. 7FFF
H
0V
Approx. 7FFF
H
20mA
Approx. 24A0
H
10V
Approx. E4C8
H
5V
Approx. E4C8
H
H
H
H
H
H
H
H
H
H
H
H