ONLINE MODULE CHANGE
(5) Resumption of control
7
7.3 Online Module Change Procedure
- 17
7.3.3 When user range setting is used and initial setting was made with GX Configurator-DA (other system
(b) Click the [OK] button to leave the "Online module change" mode.
(c) Click the [Close] button to close the System monitor screen.
(d) Set digital values to the digital values (Un\G1 to Un\G6) and turn Operating
condition setting request (Y9) from OFF to ON. Turn ON the output enable/disable
flag (Y1 to Y6) of the used channel to check whether proper conversion has been
made or not.
(Be careful since analog outputs are provided actually.)
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to
redisplay the "Online module change" screen, click the [Execution] button to
resume control. The FROM/TO instruction for the module resumes.