ONLINE MODULE CHANGE
(b) Click the "Execution" button to enable a module change.
(c) After confirming that the "RUN" LED of the module has turned off, remove the
7.3.2 When industrial shipment setting is used and initial setting was made with sequence program
If the following error screen appears, click the [OK] button, dismount the module
as-is, and mount a new module.
connector and dismount the module.
Always dismount the module. If mounting confirmation is made without the module
being dismounted, the module will not start properly and the "RUN" LED will not be
lit.
7.3 Online Module Change Procedure
1
2
3
4
5
6
7
8
7
- 10