3
SPECIFICATIONS
(1) Set within the digital input range and analog output range for each output
range.
If these ranges are exceeded, the maximum resolution and accuracy may not
fall within the performance specifications. (Avoid using the dotted line area
shown in Figures 3.1 and 3.2.)
(2) In user range setting 2, the maximum and minimum output values are 6V and
-6V respectively. Obtain these values as follows using the gain and offset val-
ues.
Maximum analog output value = Gain value
Minimum analog output value = (Offset value - (Gain value - Offset value))
If a maximum or minimum value exceeds the output range, use user range
setting 3.
(3) Set the offset/gain values for the user range setting 2 *1 within a range in
which the following conditions are satisfied.
(a) Setting range is from -12 to 12 V.
(b) { (Gain value) - (Offset value) } > A
<Value of A>
Normal resolution mode
3.0V
(4) Set the offset/gain values for the user range setting 3 *2 within a range in
which the following conditions are satisfied.
(a) Setting range is from -0.5 to 6 V.
(b) { (Gain value) - (Offset value) } > A
<Value of A>
Normal resolution mode
1.5V
High resolution mode
5.0V
High resolution mode
2.6V