Mitsubishi MELSEC-Q series User Manual page 143

Gx configurator-da. channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

7
ONLINE MODULE CHANGE
(3) Mounting of new module
(4) Operation check
7.3.3 When user range setting is used and initial setting was made with GX Configurator-DA (other system
(a) Mount the dismounted module and new module to the other system.
(b) Using the G(P).OGLOAD instruction, save the user set values to the CPU device.
Refer to Appendix 1.2 for the G(P).OGLOAD instruction.
(c) Using the G(P).OGSTOR instruction, restore the user set values to the module.
Refer to Appendix 1.3 for the G(P).OGSTOR instruction.
(d) Dismount the new module from the other system, mount it to the slot from where
the old module was dismounted in the original system, and install the connector.
(e) After mounting the module, click the [Execution] button and make sure that the
"RUN" LED is lit. Module Ready (X0) remains OFF.
(a) To make an operation check, click the [Cancel] button to cancel control
resumption.
7.3 Online Module Change Procedure
1
2
3
4
5
6
7
8
7
- 16

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q66da-g

Table of Contents