When User Range Setting Is Used And Initial Setting Was Made With Gx Configurator-Da (Other System Is Available) - Mitsubishi MELSEC-Q series User Manual

Gx configurator-da. channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

7
ONLINE MODULE CHANGE
7.3.3
When user range setting is used and initial setting was made
with GX Configurator-DA (other system is available)
(1) Conversion disable
(2) Dismounting of module
7.3.3 When user range setting is used and initial setting was made with GX Configurator-DA (other system
(a) Set D/A Conversion enable/disable setting (Un\G0) for all channel conversion
disable and turn Operating condition setting request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the actual analog output value,
turn OFF Operating condition setting request (Y9).
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the
"Online module change" mode, double-click the module to be changed online to
display the "Online module change" screen.
7.3 Online Module Change Procedure
1
2
3
4
5
6
7
8
7
- 14

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q66da-g

Table of Contents