Offset/Gain Adjustment Value Specification (Un\G24); Offset/Gain Range Setting (Un\G25) - Mitsubishi MELSEC-Q series User Manual

Gx configurator-da. channel isolated digital-analog converter module
Hide thumbs Also See for MELSEC-Q series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3.4.8

Offset/gain adjustment value specification (Un\G24)

(1) This area is used to set the amount of adjustment for analog output values in the off-
set/gain setting mode.
(2) Turning the set value change request (YC) from OFF to ON increments or decrements
the analog output value by the adjustment value.
(3) The settable input range is from -3000 to 3000.
When the set value is 1000, the analog output values can be adjusted by following
value.
(4) Refer to Section 4.6 for details of offset/gain setting.
3.4.9

Offset/gain range setting (Un\G25)

(1) This area is used to change the output range in the offset/gain setting mode. Turning
ON the channel change request (YB) changes the output range into the set one.
If any value outside the setting range is set, an error occurs and the corresponding
error code (Un\G19) is stored.
(2) The channel change request (YB) must be turned ON/OFF to validate the offset/gain
range setting. (Refer to Section 3.3.2.)
(3) Refer to Section 4.6 for details of offset/gain setting.
Output range
User range setting1
User range setting2
User range setting3
Output range
User range setting 1
User range setting 2
User range setting 3
3.4.8 Offset/gain adjustment value specification (Un\G24)
Adjustment when set value is 1000
Approx. 0.86mA
Approx. 0.38V
Approx. 0.19V
Set value
000F
H
000E
H
000D
H
3.4 Buffer Memory
1
2
3
4
5
6
7
8
3
- 33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Q66da-g

Table of Contents