Section 7
7.4
MOUNTING THE TRANSDUCERS
Two mounting configurations are available. Adjacent mounting locates the two transducers alongside
each other using a single mounting chain or strap. In-Line mounting locates the two transducers axially
along the pipe using two mounting chains or straps. On metal pipes the Receive Transducer is always
located behind the Transmit Transducer. On plastic pipes the Transmit Transducer is always located
behind the Receive Transducer. In both cases, the cable entry will be on the same end of both trans-
ducers unlike the transit-time configurations. Adjacent mounting will provide the maximum sensitivity to
flow. Refer to the appropriate transducer installation drawing for the 191N1S (Installation Drawing
191N1S-7).
Connect to UP
Connect to UP
Terminal on flow
terminal on flow
computer
computer
Connect to DOWN
Connect to
Terminal on flow
DOWN terminal
computer
on flow computer
REFLEXOR MODE - ADJACENT TRANSDUCER MOUNTING
"C2" Transducers
C2 Transducers
Connect to
Connect to DOWN
DOWN Terminal
terminal on flow
on flow computer
computer
(RECEIVE)
(Receive)
NOTE: Transducer position shown is for metal pipes.
REFLEXOR MODE - IN-LINE TRANSDUCER MOUNTING
Connect to UP terminal on
Connect to UP Terminal on
flow computer (Transmit)
flow computer (TRANSMIT)
Flow Direction
Flow Direction
7-3
1010PFM-3G
"C2"
C2 Transducers
Transducers
Flow Direction
Flow Direction
"C2"
C2 Transducers
Transducers
Flow Direction
Flow Direction