6.7 MODBUS RTU Communication (For L40MR and L60MR
types)
6.7.1 Overview of Functions
The MODBUS RTU protocol enables the communication between the FP-X0 and other devices
-
(including our FP-X, FP-e, Programmable display GT series and KT temperature control).
Enables to have conversations if the master unit sends instructions (command messages) to slave
-
units and the slave units respond (response messages) according to the instructions.
Enables the communication between the devices of max. 255 units as the master function and slave
-
function is equipped.
About MODBUS RTU
The MODBUS RTU communication is a function for the master unit to read and write the data in slave
-
units communicating between them.
There are ASCII mode and RTU (binary) mode in the MODBUS protocol, however, the FP-X0 is
-
supported with the RTU (binary) mode only.
Master function
Writing and reading data for various slaves is available using the F145 (SEND) and F146 (RECV)
-
instructions.
Individual access to each slave and the global transmission is possible.
-
Slave function
If the slave units receive a command message from the master unit, they send back the response
-
message corresponding to the content.
Do not execute the F145 (SEND) or F146 (RECV) instructions when the unit is used as a slave unit.
-