Restrictions on Using Expansion FP0 Adapter (For L40/L60 only)
1.2.2
Restrictions on type of FP-X0 control units
Only one expansion FP0 adapter can be connected to FP-X0 L40 or L60 control unit.
-
Restrictions on installation positions of Expansion FP0 adapter
When connecting the expansion FP0 adapter to FP-X0 L40 or L60 control unit, only one unit can be
-
connected at the last position of the expansion bus. Cnnect it on the righ-hand side of all other FP-X
expansion units.
Up to two FP-X expansion I/O units can be installed between the control unit and expansion FP0
-
adapter.
Restrictions on installation positions of FP0/FP0R units
Up to three FP0/FP0R expansion units and advanced units can be installed on the right-hand side of
-
the expansion FP0 adapter.
Note) Install the FP0 thermocouple unit on the right side of all other expansion units. If it is installed on
-
the left side, the total precision will deteriorate.
Install the FP0 CC-Link slave unit on the right side of the other expansion units. There is no expansion
-
connector on the right side.