3.1.3 Input and output specifications
Input specifications
Item
Insulation method
Rated input voltage
Operating voltage range
Rated input current
Input points per common
Min. on voltage/Min. on current
Max. off voltage/Max. off current
Input impedance
Response time
Operating mode indicator
EN61131-2Applicable type
Circuit diagram
Relay output specifications
Item
Insulation method
Output type
Rated control capacity
Output points per common
off→on
Response time
on→off
Mechanical
Lifetime
Electrical
Surge absorber
Operating mode indicator
Note) Resistance load
Circuit diagram
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Optical coupler
24 V DC
21.6 to 26.4 V DC
Approx. 4.3 mA
8 points/common
(Either the positive or negative of input power supply can be
connected to common terminal.)
19.2 V DC/3 mA
2.4 V DC/1 mA
Approx. 5.6 kΩ
off→on
0.6 ms or less
on→off
0.6 ms or less
LED display
TYPE3 (however, according to the above specifications)
Relay insulation
1a output (Relay cannot be replaced.)
Note)
2 A 250 V AC, 2 A 30 V DC
(6 A or less/common)
1 point/common,
3 points/common
Approx. 10 ms
Approx. 8 ms
20 million times or more (Frequency of switching: 180 times/min.)
100 thousand times or more (Frequency of switching at the rated
control capacity: 20 times/min.)
None
LED display
Description
E16
: R1=5.6 k Ω
R2=1 kΩ
Description
E16/E14
E30
16 points/common
E30
(8 A or less/common)
1 point/common,
4 points/common