Panasonic FP-X0 L14R User Manual page 134

Table of Contents

Advertisement

7.4.3 I/O Allocation
Double pulse input driver
(CW pulse input and CCW pulse input method)
Two output contacts are used as a pulse output for "CW, CCW".
-
The I/O allocation of pulse output terminal and home input is determined by the channel used.
-
Near home input is substituted by allocating the desired contact and turning on and off the <bit4> of
-
special data register DT90052.
Set the control code for F171 (SPDH) instruction to "CW/CCW".
-
<When using CH0>
* X0 or any other input can be specified for the
near home input.
Single pulse input driver
(pulse input and directional switching input method)
One output point is used as a pulse output and the other output is used as a direction output.
-
The I/O allocation of pulse output terminal, direction output terminal, and home input is determined by
-
the channel used.
Near home input is substituted by allocating the desired contact and turning on and off the <bit4> of
-
special data register DT90052.
Up to four driver systems can be connected.
-
Specify "PLS+SIGN" for the control code of F171 to F177 instructions.
-
<When using CH0>
* X0 or any other input can be specified for the
near home input.
Reference: <7.2.1 Table of Specifications>
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
<When using CH2>
* X1 or any other input can be specified for the
near home input.
<When using CH2>
* X1 or any other input can be specified for the
near home input.