Panasonic FP-X0 L14R User Manual page 25

Table of Contents

Advertisement

2.3.3 Output Specifications (L14: From Y2, L30/L40/L60: From Y4)
Item
Insulation method
Output type
Rated control capacity
(Resistance load)
Output points per common
Response time
Mechanical
Lifetime
Electrical
Surge absorber
Operating mode indicator
Note) There are restrictions on the rated current for each output block. Each usable rated current is as
below.
L14: Y2 to Y5 (4 points) Max. 6A in total
L30: Y4 to YD (10 points) Max. 8A in total
L40: Y4 to YFD (12 points) Max. 8A in total
L60: Y4 to YB (8 points) Max. 8A in total, YC to Y1B (16 points) Max. 8A in total
Circuit diagram
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Relay insulation
1a output (Relay cannot be replaced)
2 A 250 V AC, 2 A 30 V DC (per point)
Note)
1 point/common x 2, 2 points/common x 1 (L14)
2 points/common x 1, 4 points/common x 2 (L30)
1 point/common x 2, 2 points/common x 1, 4 points/common x 2 (L40)
4 points/common x 6 (L60)
off→on
Approx. 10 ms
on→off
Approx. 8 ms
20 million times or more (Frequency of switching: 180 times/min.)
100 thousand times or more (Frequency of switching at the rated control
capacity: 20 times/min.)
None
LED display
Description