The explanation below shows the case that pulses are output from Y0 when using forward rotation and
Y1 when using reverse rotation with the following conditions; Initial speed: 1 kHz, Target speed: 7kHz,
Acceleraiton time: 100 ms, Deceleration time: 100 ms.
Example of timing chart
Data table
Data
register
Setting item (Unit)
No.
DT300
Control code
DT302
Initial speed (Hz)
DT304
Target speed (Hz)
DT306
Acceleration time (ms) K100
DT308
Deceleration time (ms) K100
DT310
Target value (pulses ) K0
Note) When the control code is set to Type 0 (No target value), specify "0" for the target value.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Example of sample
program
Type 0 (No target value)
Output type: CW/CCW
H1000 0000 (Forward)
H1000 0010 (Reverse)
K1000
K7000
Settable range
Set according to the control code
on the next page.
K1 to K20000 (L14/L30 type)
K1 to K50000 (L40/L60 type)
K1 to K20000 (L14/L30 type)
K1 to K50000 (L40/L60 type)
K1 to K32760
K1 to K32760
K-2,147,483,648 to K+2,147,483,647