11.2.3 Precautions When Using a Control Instruction
If a leading edge detection instruction is in a control instruction, it will be executed only under the
-
following condition: The leading edge detection instruction was off when the execution condition of the
previous control instruction was reset, and the leading edge detection instruction is on when the
execution condition of the current control instruction becomes on.
When a leading edge detection instruction is used with an instruction which changes the order of
-
instruction execution such as MC, MCE, JP or LBL, the operation of the instruction may change as
follows depending on input timing. Take care regarding this point.
<Example 1> Using the DF instruction between MC and MCE instructions
<Example 2> Using the CT instruction between JP and LBL instructions